Measuring medium |
various liquid, gas or steam compatible with 304、316 stainless steel |
Measuring range |
-100kpa...0~20kpa...100MPA (optional) |
Overload pressure |
2 times full scale |
output signal |
4~20mA (two-wire system), 0-10VDC, 0-5VDC, 1-5VDC (three-wire system) |
Supply voltage |
8~32VDC |
Operating temperature |
-40-125℃ |
Temperature compensation |
-10-70°C |
Relative humidity |
0%~100% |
Rise Time |
90% FS can be reached in less than 5 milliseconds |
Accuracy |
0.25%FS, 0.5%FS, 1%FS |
stability |
Typical: ±0.1%FS Very large: ±0.2%FS |
Medium contact material |
304、316 stainless steel |
Shell material |
304 or 316 stainless steel |
Installation method |
Threaded installation |
Lead way |
Four-core shielded cable (protection grade IP68), aviation plug, DIN connector (protection grade IP65) |
This series of constant pressure water supply pressure transmitters use high-precision, high-stability pressure sensor components and special IC circuits from internationally renowned companies. After high-reliability amplifier circuits and precise temperature compensation, the absolute pressure or gauge pressure of the measured medium is converted. Standard electrical signals such as 4~20mA, 0~5VDC, 0~10VDC and 1~5VDC 。It is widely used in the detection and control of fluid pressure in industries such as industrial control, process detection, chemical industry, electric power, hydrology, geology, etc. High-quality sensors, hermetic welding packaging technology and perfect assembly process ensure the excellent quality and very good performance of this product. The product has a variety of interface forms and a variety of lead methods, which can meet the needs of customers to the greatest extent, and is suitable for use with various measurement and control equipment.
Compensation in the whole temperature zone, with little temperature influence;
Short circuit protection and reverse polarity protection;
Zero point and full scale output are adjustable;
Output 0~10/20mADC, 4~20mADC; 0~5/10VDC, 1~5VDC.
Water level measurement of various water equipment, underground water level measurement, building water supply system, river water power station measurement.